AC power: 220VAC, 50Hz, 2.3 amps
Wire size: minimum #14 AWG (2.0 mm2) with 600V insulation
Battery (lead acid only)
Maximum Charging Circuit: Normal Flat Charge-27.6V@0.8amp
Maximum Charger Capacity:18Amp Hour batter
Sount Output Device Circuits
General Alarm Zones 1 through 16
Operation: All zones Class B
Normal Operating Voltage: Nominal 24VDC(ripple≤100mV maximum)
Alarm Current: 15mA threshold
Short Circuit Current:42mA maximum
Maximum Loop Resistance: 100 ohms
End-of-Line Resistor:4.7K, 1/2 wait
Detector Loop Current is sufficient to ensure operation of two alarmed detectors per zone
Standby Current: 7.26mA
Three Relays Output
Relay contact eating: 2.0amps@30VDC (resistive), 2.0 a,ps@30VAC (resistive)
Nonresettable 24VDC Power
Maximum ripple voltage:10mV RMS
Operating Voltage nominal 24 volts
Total DC current available from this output is up to 500mA
Recommended maximum Standby current is 150mA